Research Article | | Peer-Reviewed

A Method for Determination of Hydrocarbon and Nitrogenous Biochemical Oxygen Demands in Natural Waters by Manometric Method

Received: 5 November 2024     Accepted: 18 November 2024     Published: 29 November 2024
Views:       Downloads:
Abstract

The aim of the work was the simultaneous determination of hydrocarbon biochemical oxygen demand - cBOD and nBOD (nitrogen) in the same water sample without using a nitrification inhibitor by the manometric method. Daily measurements of cBOD are determined by recording the pressure drop resulting from the absorption of carbon dioxide released by the oxidation of hydrocarbon organic matter by microorganisms with KOH (potassium hydroxide). Here, the processes of oxidation of mineral substances in water and especially the developing nitrification processes, which absorb oxygen dissolved in water and cause an additional pressure drop in the vessel, are a disturbing factor, for the measurement of which, in the daily 24-hour cycle of registrations, it is recommended to close the absorption hole of the vial with KOH for 8 hours. The 24-hour nBOD and cBOD results are calculated from the result of the pressure drop in these 8 hours. In the paper, in the form of a table, the detailed form of calculation of the recorded results of BODs at two pH-s of a natural water sample within 1-20 days is given. The possibility of anthropogenic impact assessment using this method is shown on the example of natural water. It is concluded that with the proposed method of measuring BODs records the complete and separate results of cBOD are recorded under conditions of developing nitrification in water. All information from both nitrification and BOD-full is recorded simultaneously, which gives a complete picture of the overall oxygen balance in the water. The proposed method is practically applicable and fully comparable with the results obtained by the standard manometric method.

Published in Modern Chemistry (Volume 12, Issue 4)
DOI 10.11648/j.mc.20241204.12
Page(s) 82-88
Creative Commons

This is an Open Access article, distributed under the terms of the Creative Commons Attribution 4.0 International License (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted use, distribution and reproduction in any medium or format, provided the original work is properly cited.

Copyright

Copyright © The Author(s), 2024. Published by Science Publishing Group

Keywords

nBOD, cBOD, BOD Full, Method, Nitrification, Total Oxygen Balance

1. Introduction
In modern conditions, the use of improved and highly accurate research methods is becoming particularly relevant. Biochemical oxygen demand (BOD) studies are widely used in ecological water monitoring. BOD measurement reflects the processes of decomposition of organic substances in water. It involves two phases: carbonic, during which oxygen is consumed for the microbial decomposition of carbon compounds (cBOD), and nitrogen, during which mineral nitrogen compounds are oxidized (nBOD) . It reflects the degree of water pollution according to the amount of organic matter in the water that can be oxidized by microorganisms . The great advantage of the manometric method over other BOD determination methods is that it provides dynamic determination of practically all BOD from day 1 to day 20 or more days in the same water sample. However, the exact determination of cBOD (hydrocarbon) is always hindered by the oxidation processes of partial mineral substances (sulfides, iron, etc.), and especially the nitrification processes developing in water , for the inhibition of which, inhibitor thiourea or allylthiourea is added to the water sample .
An attempt was made to quantitatively calculate nitrification in water with and without an inhibitor using manometric method by measuring BOD-5 . Other researchers have also conducted longer studies (30 days) in order to study in more detail the characteristics of the transformation of organic matter in natural waters, but using an inhibitor. Sometimes, especially in long-term experiments, the nitrifying bacteria adapt to the inhibitor and nitrification develops at some point, distorting the results. And increasing the concentration of the inhibitor suppresses the activity of saprophytic bacteria, which ensure the normal course of cBOD.
The last best method for clean determination of cBOD-5 (carbonic) without the use of an inhibitor by manometric method is the carbonate turbidimetric method . It is based on the fact that no carbon dioxide is produced in nitrification and during the oxidation of minerals, and therefore only carbon dioxide separated by hydrocarbon oxidation is absorbed by potassium hydroxide. However, this method determines the specific cBOD-5 by stopping the experiment and recording the accumulated carbon dioxide. In this mode, there is no consecutive dynamic survey from the same water sample.
Another important aspect of the issue is that by passing the nitrification process or suppressing it with an inhibitor, we lose information about the amount of oxygen spent on that process, which plays a very large role in the overall oxygen balance of natural waters, for example in rivers .
In order to overcome these issues and to obtain full information about the total consumption of oxygen in water and all BODs, we made a technical innovation in the manometric method , the essence of which is to interrupt the absorption of carbon dioxide gas by potassium hydroxide in the system in a periodic discrete period and by computational method deriving nBOD and cBOD that was used in this study and is detailed here.
2. Method
2.1. Sample Collection
The investigated waters were taken from three observation points.
№1-observation point - Hrazdan River in the zone of Yerevan city under the Kievyan bridge, (9.03.2024), water temperature 6.5°C, natural pH=8.3 and adjusted pH=7.0 with sulfuric acid.
№2 - observation point - Hrazdan River before Bzhni village (23.06.2024), water temperature is 15.5°C, natural pH=8.4.
№3 - observation point - Hrazdan River after Bzhni village (23.06.2024) water temperature is 15.6°C, natural pH=8.4.
2.2. BOD Determination.
BOD tests were performed with the device whose block diagram is shown in Figure 1 below.
Figure 1. Block diagram of BOD measurement device. Explanation in the text.
The water sample is placed in a vessel (G) and hermetically sealed with a stopper (C) to which a manometer (B) is attached to measure the pressure in the vessel.
For the absorption of carbon dioxide in the vessel, a vial (F) containing 5-6 drops of 45% KOH is fixed in the air space under the stopper, at the entrance of which a magnetic valve (D) is fixed to which when a permanent magnet (E) is brought near (from the outside of the vessel) the KOH hole is closed. After being closed for 8 hours, the KOH hole opens when the magnet is moved from the opposite side of the vessel. After 16 hours it closes again for 8 hours and so on every day. Closing and opening the hole of the vial with KOH in the specified way does not at all break the hermeticity of the vessel with the water sample and the continuous recording of pressure differences. To enhance the gas exchange of carbon dioxide and oxygen in the water sample, the water sample is stirred with a magnet (H) on a magnetic stirrer (L). BOD was determined in a 188 ml water sample at 20.0°C in the dark in incubator (A). All BOD results were recalculated to mg O2/liter according to the formula given .
2.3. Sample Analyses
All waters were filtered through a Gas-38 filter to remove large zooplankton prior to determination. The amount of easily oxidizable organic matter in water samples was measured by determining the degree of permanganate oxidation (PO) of water by Kubel's method . Total hardness (TH) of water was determined complexonometrically . The concentration of hydrogen ion in water was pH-measured with a pH-121 device. The results were processed statistically .
3. Results and Discussion
BOD-1-20 was analyzed in the water sample taken from observation point №1 at its own pH=8.3 and adjusted pH=7.0. In order to show in detail the calculation of BODs by the proposed method, the results obtained directly from two characteristic samples and the way of their calculation are given in the Table 1.
Table 1. The form of calculation of BOD (mgO2/l) 1-20 in the waters of Hrazdan River № 1 observation point at two pH levels.

pH=7.0

pH=8.3

Column

1

2

3

4

5

6

7

8

9

10

Bod1-20

8-hournBod

24-hournBod

Bod full

Bod c

Bod Full st.

8-hournBod

24-hournBod

Bod full

Bod c

Bod Full st.

1

0.09

0.39

0.60

0.21

0.15

0.03

0.18

0.27

0.09

0.63

2

0.18

0.63

0.99

0.36

0.45

0.09

0.36

0.51

0.15

0.78

3

0.24

0.75

1.35

0.60

0.99

0.15

0.45

0.69

0.24

0.91

4

0.27

0.81

1.14

0.33

0.66

0.15

0.66

0.93

0.27

1.05

5

0.27

0.84

1.14

0.30

0.79

0.30

1.11

1.35

0.24

1.29

1-5

<->

3.42

5.22

1.80

3.00

<->

2.76

3.75

0.99

4.68

6

0.30

0.90

1.14

0.24

1.11

0.45

1.56

1.65

0.09

1.65

7

0.30

0.96

1.20

0.24

2.07

0.60

1.92

2.01

0.09

1.89

8

0.33

0.99

1.26

0.27

1.41

0.69

1.98

2.04

0.06

2.07

9

0.33

0.99

1.26

0.27

1.53

0.63

1.80

2.04

0.24

1.95

10

0.33

0.93

1.26

0.33

1.41

0.57

1.56

2.13

0.57

1.65

5-10

1-10

<->

<->

4.77

8.19

6.12

11.3

1.35

3.15

7.53

10.5

<->

<->

8.82

11.6

9.87

13.6

1.05

2.04

9.21

13.9

11

0.30

0.84

1.20

0.36

1.41

0.48

1.26

2.10

0.84

1.71

12

0.27

0.81

1.26

0.45

1.38

0.36

0.99

1.83

0.84

1.59

13

0.27

0.81

1.23

0.42

1.44

0.30

0.90

1.71

0.91

1.44

14

0.27

0.78

1.20

0.42

1.32

0.27

0.78

1.32

0.54

1.29

15

0.24

0.66

1.11

0.45

1.17

0.24

0.69

1.23

0.54

1.02

10-15

1-15

<->

<->

3.90

12.1

6.00

17.3

2.10

5.25

6.72

17.3

<->

<->

4.62

16.2

8.19

21.8

3.57

5.61

7.05

20.9

16

0.21

0.57

0.84

0.27

0.90

0.21

0.51

0.90

0.39

0.99

17

0.18

0.54

0.81

0.24

0.81

0.12

0.27

0.66

0.39

0.66

18

0.18

0.57

0.81

0.24

0.75

0.06

0.24

0.54

0.30

0.63

19

0.21

0.57

0.84

0.27

0.72

0.09

0.24

0.54

0.30

0.57

20

0.18

0.54

0.75

0.21

0.72

0.06

0.18

0.45

0.27

0.45

15-20

<->

2.79

4.05

1.23

3.90

<->

1.44

3.09

1.65

3.30

1-20

<->

14.9

21.4

6.48

21.2

<->

17.6

24.9

7.25

24.2

Note: the average statistical variation of the results is ±0.02, <-> it is not necessary the total calculation
Columns 1 and 6 of the table give direct readings of O2 absorption (at pH=7.0 and pH=8.3, respectively) recorded with the hole of the KOH vial closed for 8 hours to show the form of nBOD (nitrogen) calculation.
Columns 2 and 7 show the calculated amount of absorbed O2 in 24 hours with the hole of the KOH vial closed (conventional nBOD), which is theoretically equal to three times the value of absorbed O2 in 8 hours. However for the most accurate calculation, it is necessary to take three times the arithmetic mean value of the results of 8 hours of closed KOH of that day and 8 hours of closed KOH of the next day, which was used in all the results. Such an averaged calculation more accurately reflects the tendencies (dynamics) of the possible development or decrease of nitrification in the results of the following days. In later stages of the records, when the results are slow to change or repeat, for example, for the 24 hours nBOD on day 20, three times of the 8 hours recorded result can be taken, as shown in Table 1 for BOD-20 only.
Columns 3 and 8 of the table give the BOD-full results, which directly show the change in the manometer reading of 8 hours before closing the hole in the KOH vial and the result recorded after 16 hours of opening the hole. In these 24 hours (8+16 hours), the result of the pressure drop caused by the absorbed O2 includes, firstly, the absorption of O2 in the water by autonomous oxidative processes, which are not accompanied by the release of CO2 (oxidation of mineral substances, nitrification - conditional nBOD), and secondly due to the absorption of CO2 gas by KOH, (which is equivalent to the absorption of the same amount of O2) accumulated in the vessel in the state of the closed hole of the KOH vial at 8 hours, and after opening the KOH hole for 16 hours, due to the cost of O2 in cBOD.
Columns 4 and 9 of the table give cBOD values, which are calculated by the difference between the daily readings of BOD-full and nBOD.
Columns 5 and 10 of the table show the results of the BOD full (st.) standard recorded in the manometric method in days 1-20 in parallel water samples with the hole of the KOH vial always open.
This appears to be a test for the comparability of the BOD-full results (columns 3 and 8) measured with the KOH hole closed and open. According to the table they are completely comparable.
In table 1, from the observation of the dynamics of the results of nBOD (24hours) at pH=7.0 (2-column) and pH=8.3 (7-column), it can be seen that at pH=8.3 a strong pronounced outbreak of nitrification is observed from 5 to 15 days, with a sharp peak on the 8th day. This is a typical expressed dynamics of nitrification, which repeats the dynamics of NH4+ (ammonium) ion transformation in river water during the days .
At pH=7.0, nitrification also proceeds but with a weak expressed maximum.
Table 2 shows the average results of three experiments at the same pH-s from that same №1 observation point - with only consecutive 5-day cumulative BOD values within 20 days.
Table 2. The average results of BOD (mgO2/l) of three experiments in the waters of observation point №1 of Hrazdan River at two pH levels and relative standard deviation in % (RSD%) for the BOD 1-20。

Bod days

pH=7.0

pH=8.3

Bod-full st.

Bod-full

nBod

cBod

Bod-full st.

Bod-full

nBod

cBod

1-5

3.84

5.04

3.15

1.82

6.63

6.42

5.77

1.65

5-10

6.78

6.72

4.83

1.89

9.45

9.30

7.47

1.83

1-10

10.62

11.76

7.98

3.78

16.08

15.72

12.24

3.48

10-15

6.60

6.30

4.23

2.07

5.64

6.21

3.75

2.46

1-15

17.22

18.06

12.21

5.85

21.72

21.93

15.99

5.94

15-20

3.96

3.54

2.28

1.26

2.46

2.37

1.11

1.26

1-20

21.18

21.60

14.49

7.11

24.18

24.3

17.10

7.20

RSD%

3.4%

2.0%

2.3%

11.0%

6.2%

5.3%

9.0%

1.3%

As can be seen from the dynamics of the results of Table 2 and the total results of BOD-1-20, at pH=8.3 the nitrification processes are noticeably developing and on the 20th day the total nBOD has significantly higher results than at pH=7.0 (about 12 %). The reason for this may be that pH=8.3 is close to the optimum of the nitrification process (pH=7.6-8.6). Comparing the cBOD recorded dynamics of the sum results of 1-5; 5-10; 10-15 and 15-20 at both pHs, the expressed peak cBOD in 10-15 is observed, which indicates that the water is dominated by hard-to-oxidize organic substances.
Comparison of BOD-full st. (KOH hole always open) 1-20 total results in the table with discrete records (KOH hole 8 hours closed and 16 hours open) with BOD-full 1-20 results at pH=7.0 (21.18 and 21.60 mg O2/l, relative error 1.9%) and at pH=8.3 (24.18 and 24.30 mg O2/l, relative error 0.5%) show very close comparable results. This confirms the comparability of the proposed discrete method of BOD recording with the standard method of the manometric method. The RSD of this method is satisfactory and comparable to other methods.
In order to clarify the possibility of registering subtle changes in BOD in the proposed method, water quality indicators were studied before (№2 -observation point - not affected by anthropogenic influence) and after (№3 observation point, after the village was affected by anthropogenic influence) of Bzhni village of the Hrazdan River. Permanganate oxidation (PO) was equal to 2.20 mg O/liter and water hardness was 5.6 mg-eqv/l in observation point №2. BOD results are given in Table 3. At the same time, permanganate oxidation in observation point №3 was equal to 3.80 mg O/l and water hardness was 5.8 mg-eqv/l. BOD results are given in Table 3 measured at natural pH=8.4.
Table 3. BOD (mg O2/l) results before (№2) and after (№3) Bzhni village and relative standard deviation in % (RSD%) for the BOD 1-20.

Bod Days

№2- observation point

№3- observation point

Bod-full st.

Bod-full

nBod

cBod

Bod- full st.

Bod-full

nBod

cBod

1-5

3.84

4.86

3.03

1.83

3.06

5.94

3.78

2.16

5-10

5.79

4.92

2.25

2.67

7.35

6.49

3.24

4.15

1-10

9.63

9.78

5.28

4.50

10.41

12.33

7.02

5.31

10-15

3.12

3.00

1.71

1.29

5.07

4.32

2.22

2.10

1-15

12.75

12.78

6.99

5.79

15.48

16.65

9.24

7.41

15-20

2.49

2.88

1.92

0.96

3.45

2.61

0.72

1.89

1-20

15.24

15.66

8.91

6.75

18.93

19.26

9.96

9.30

RSD%

2.6%

6.0%

3.7%

3.0%

8.2%

7.9%

4.1%

3.9%

In Table 3, the comparison of the results of BOD-full st. (KOH hole always open) with discrete records (KOH hole 8 hours closed and 16 hours open) with the results of BOD-full 1-20 very close results are observed in both observation points, the difference of which is 2.7% in observation point № 2 and 1.7% in № 3. At the same time, it can be seen from Table 3 that the total oxygen balance calculated by the results of BOD-full 1-20 is 23% worse after Bzhni village (19.26 mg O2/l) than before Bzhni village (15.66 mg O2/l). The results of cBOD 1-20 and nBOD 1-20 obtained by discrete registrations in Table 3 show that the reason for this bad oxygen balance (high oxygen consumption) after the village of Bzhni is caused by a significantly high level of cBOD (9.30 mg O2/ l) than before Bzhni village (6.75 mg O2/l). It is a consequence of human factors, domestic and technical direct discharges into the river, as a result of which a significant increase in the PO indicator is also recorded - from 2.20 mg O/l to 3.80 mg O/l. Water hardness increases slightly. Deterioration of water quality in this observation point was also recorded in studies of previous years .
Table 3 also shows the pattern of cBOD dynamics in two observation points. Maximum values are recorded in cBOD 5-10 compared to cBOD 1-5; 10-15 and 15-20 testimonies. The nBOD results are also high after Bzhni village and show monotonically decreasing dynamics.
4. Conclusion
1) Performance of discrete periods of carbon dioxide absorption by potassium hydroxide in BOD measurements ensures complete and discrete cBOD results from the same water sample in intact water during 1-20 days of developing nitrification. Not using a nitrification inhibitor ensures the full development of natural microflora during experiments.
2) All information from both nitrification and BOD-full is recorded simultaneously, which gives a complete picture of the total oxygen balance in the water. Obtaining this information from the same water sample simplifies experiment setup, reduces water consumption and increases the reliability of results.
3) The proposed method is practically applicable and fully comparable with the results obtained by the standard manometric method.
4) The method allows evaluating changes in natural water quality after anthropogenic impacts. By the proposed method allows expanding the applicability of the manometric method.
Abbreviations

BOD

Biochemical Oxygen Demand

cBOD

Hydrocarbon Biochemical Oxygen Demand

nBOD

Nitrogenous Biochemical Oxygen Demand

BOD-full

Biochemical Oxygen Demand Full

KOH

Potassium Hydroxide

CO2

Carbon Dioxide

PO

Permanganate Oxidation

TH

Total Hardness

Author Contributions
Suren Sargsyan is the sole author. The author read and approved the final manuscript.
Conflicts of Interest
The author declares no conflicts of interest.
References
[1] Konig A., Bachmann T. T., Metzger J. W., Schmid R. D. Disposable sensor for measuring the biochemical oxygen demand for nitrification and inhibition of nitrification in wastewater. Springer-Verlag, Appl. Microbiol. Biotechnol. 1999, 51, pp. 112-117.
[2] Dhall P, Kumar R, Kumar A. Biodegradation of sewage wastewater using Autochthonous bacteria. Scientific World Journal 2012: 861903.
[3] Water quality – Determination of biochemical oxygen demand after n days (BODn) – Part 2: Method for undiluted samples. Norm ISO 5815-2: 2003.
[4] Geneva, International Organization for Standardization Publ., 2003, 13 pp. RD 52.24.420–2006. Biokhimicheskoe potreblenie kisloroda v vodakh. Metodika vypolneniya izmerenii sklyanochnym metodom (Biochemical Oxygen consumption in waters. The light-and-dark-bottle measurement procedure). Rostov-na-Donu: GKhI, 2006, 19 p. (in Russian)
[5] Su JJ, Liu BY, Chang YC. Identifying an interfering factor on chemical oxygen demand (COD) determination in piggery wastewater and eliminating the factor byanindigenous Pseudomonas stutzeri strain. Lett Appl Microbiol, 2001, 33(6), 440-444.
[6] Hur J, Cho J. Prediction of BOD, COD, and total nitrogen concentrations in a typical urban river using a fluorescence excitation-emission matrix with Parafac and UV Absorption Indices. Sensors. 2012, 12(1), 972-986.
[7] Wood L. B., Hurley B. J., Matthews P. J. Some observations on the biochemistry and inhibition of nitrification. Wat. Res. 1981, 15, 543-551.
[8] Feliatra F., Bianchi M. Rates of nitrification and carbon uptake in the Rhone River plume (Northwestern Mediterranean Sea). Microb. Ecol. 1993, 26, 21-28.
[9] Grunditz C., Dalhammar G. Development of nitrification inhibition assays using pure cultures of Nitrosomonas and Nitrobacter. Wat. Res. 2001, 35(2), 433-440.
[10] Water quality – Determination of biochemical oxygen demand after n days (BODn) – Part 1: Dilution and seeding method with allylthiourea addition. Norm ISO 5815-1: 2003. Geneva, International Organization for Standardization Publ. 2003, 15 pp.
[11] Polak J. Nitrification in the surface water of the Wloclawek Dam Reservoir. The Process Contribution to Biochemical Oxygen Demand (N-BOD). Polish Journal of Environmental Studies. 2004, 13(4), 415–424.
[12] Ostapenia A. P., Parparov A., Berman T. Lability of organic carbon in lakes of different trophic status // Freshwater Biol. 2009, 54, pp. 1312–1323.
[13] Sabylina A. V., Lozovik P. A., Zobkov M. B. Water chemistry in Onega Lake and its tributaries. Water Resources. 2010, 37(6), 842–853.
[14] Sullivan A. B., Snyder D. V., Rounds S. A. Controls on biochemical oxygen demand in the upper Klamath River, Oregon. Chem. Geol. 2010, 269, 12–21.
[15] Rezvani H., Mirghaffari N., Marzban M., Marzban AR. Determination of biochemical oxygen demand (BOD) without nitrification and mineral oxidant bacteria interferences by carbonate turbidimetry. Research Journal of Pharmaceutical, Biological and Chemical Sciences. 2014, 5(5), 90-95.
[16] Gorland J. H. N. Nitrification in the river Trent. Mathematical models of water pollution. M. Mir. 1981, pp. 201-228 (in Russian).
[17] Vavilin V. A. 1983. Nonlinear models of biological purification and self-purification processes in rivers. M. Nauka. 1981, p. 158. (in Russian)
[18] Sargsyan S. A. A method and adaptation for determining biochemical oxygen demand. Patent of RA. № 891Y G01N 33/00, registered in 12.02.2024 (in Armenian).
[19] Lurye U. U.(ed.) Uniform methods for water analysis. Moscow, Khimia, 1971, 374 pp. (in Russian).
[20] Lurye U. U.(ed.) Uniform methods for water analysis. Publ. 2, Moscow, Khimia, 1973, 376 pp. (in Russian).
[21] Plakhinsky N. A. Biometrics. Moscow, MGU, 1970, 367 pp. (in Russian).
[22] Ryzhakov A. V. Kinetic parameters of the transformation of nitrogen-contaning compounds in natural water. Environmental Chemistry. 2012, 21(2), 117-124 (in Russian).
[23] Yurchenko V., Radionov M., Melnikova O. Kinetic parameters of nitrification in a water basin, which is a potable water source. Ecological Sciences. 2019, 1(24), 121-125. (in Ukraine).
[24] Arutunyan S. A. Oganesyan R. O. Grigoryan V. G. Dynamics of changes in the quality of waters of the Razdan River. Arminian journal of ecology. 2002, (1), 107-114 (in Russian)
[25] Kobelyan R. O. Assessment of the water quality of Hrazdan River according to microbiological indications. Biol. Arm. Journal. 2017, 4(69), 35-38 (in Armenian).
[26] Sargsyan S. A., Kobelyan P. O. Study of some hydrochemical indicators of water and the number of saprophytic bacteria in the autumn period along theriver Hrazdan. Water: Chemictry and Ecology. 2019, (10-12) pp. 149–153.
Cite This Article
  • APA Style

    Sargsyan, S. (2024). A Method for Determination of Hydrocarbon and Nitrogenous Biochemical Oxygen Demands in Natural Waters by Manometric Method. Modern Chemistry, 12(4), 82-88. https://doi.org/10.11648/j.mc.20241204.12

    Copy | Download

    ACS Style

    Sargsyan, S. A Method for Determination of Hydrocarbon and Nitrogenous Biochemical Oxygen Demands in Natural Waters by Manometric Method. Mod. Chem. 2024, 12(4), 82-88. doi: 10.11648/j.mc.20241204.12

    Copy | Download

    AMA Style

    Sargsyan S. A Method for Determination of Hydrocarbon and Nitrogenous Biochemical Oxygen Demands in Natural Waters by Manometric Method. Mod Chem. 2024;12(4):82-88. doi: 10.11648/j.mc.20241204.12

    Copy | Download

  • @article{10.11648/j.mc.20241204.12,
      author = {Suren Sargsyan},
      title = {A Method for Determination of Hydrocarbon and Nitrogenous Biochemical Oxygen Demands in Natural Waters by Manometric Method
    },
      journal = {Modern Chemistry},
      volume = {12},
      number = {4},
      pages = {82-88},
      doi = {10.11648/j.mc.20241204.12},
      url = {https://doi.org/10.11648/j.mc.20241204.12},
      eprint = {https://article.sciencepublishinggroup.com/pdf/10.11648.j.mc.20241204.12},
      abstract = {The aim of the work was the simultaneous determination of hydrocarbon biochemical oxygen demand - cBOD and nBOD (nitrogen) in the same water sample without using a nitrification inhibitor by the manometric method. Daily measurements of cBOD are determined by recording the pressure drop resulting from the absorption of carbon dioxide released by the oxidation of hydrocarbon organic matter by microorganisms with KOH (potassium hydroxide). Here, the processes of oxidation of mineral substances in water and especially the developing nitrification processes, which absorb oxygen dissolved in water and cause an additional pressure drop in the vessel, are a disturbing factor, for the measurement of which, in the daily 24-hour cycle of registrations, it is recommended to close the absorption hole of the vial with KOH for 8 hours. The 24-hour nBOD and cBOD results are calculated from the result of the pressure drop in these 8 hours. In the paper, in the form of a table, the detailed form of calculation of the recorded results of BODs at two pH-s of a natural water sample within 1-20 days is given. The possibility of anthropogenic impact assessment using this method is shown on the example of natural water. It is concluded that with the proposed method of measuring BODs records the complete and separate results of cBOD are recorded under conditions of developing nitrification in water. All information from both nitrification and BOD-full is recorded simultaneously, which gives a complete picture of the overall oxygen balance in the water. The proposed method is practically applicable and fully comparable with the results obtained by the standard manometric method.
    },
     year = {2024}
    }
    

    Copy | Download

  • TY  - JOUR
    T1  - A Method for Determination of Hydrocarbon and Nitrogenous Biochemical Oxygen Demands in Natural Waters by Manometric Method
    
    AU  - Suren Sargsyan
    Y1  - 2024/11/29
    PY  - 2024
    N1  - https://doi.org/10.11648/j.mc.20241204.12
    DO  - 10.11648/j.mc.20241204.12
    T2  - Modern Chemistry
    JF  - Modern Chemistry
    JO  - Modern Chemistry
    SP  - 82
    EP  - 88
    PB  - Science Publishing Group
    SN  - 2329-180X
    UR  - https://doi.org/10.11648/j.mc.20241204.12
    AB  - The aim of the work was the simultaneous determination of hydrocarbon biochemical oxygen demand - cBOD and nBOD (nitrogen) in the same water sample without using a nitrification inhibitor by the manometric method. Daily measurements of cBOD are determined by recording the pressure drop resulting from the absorption of carbon dioxide released by the oxidation of hydrocarbon organic matter by microorganisms with KOH (potassium hydroxide). Here, the processes of oxidation of mineral substances in water and especially the developing nitrification processes, which absorb oxygen dissolved in water and cause an additional pressure drop in the vessel, are a disturbing factor, for the measurement of which, in the daily 24-hour cycle of registrations, it is recommended to close the absorption hole of the vial with KOH for 8 hours. The 24-hour nBOD and cBOD results are calculated from the result of the pressure drop in these 8 hours. In the paper, in the form of a table, the detailed form of calculation of the recorded results of BODs at two pH-s of a natural water sample within 1-20 days is given. The possibility of anthropogenic impact assessment using this method is shown on the example of natural water. It is concluded that with the proposed method of measuring BODs records the complete and separate results of cBOD are recorded under conditions of developing nitrification in water. All information from both nitrification and BOD-full is recorded simultaneously, which gives a complete picture of the overall oxygen balance in the water. The proposed method is practically applicable and fully comparable with the results obtained by the standard manometric method.
    
    VL  - 12
    IS  - 4
    ER  - 

    Copy | Download

Author Information